Technical Bulletin

Offset the Potential Corrosive Effect of Chlorides in a Concrete Mix Using Chryso®DCI – TB-0901

14 June 17

Chryso®DCI® Corrosion Inhibitor may be used to offset the corrosive effects of chloride ions found in steel reinforced concrete. Chloride ions in the form of salts may combine with oxygen and moisture in concrete and corrode the embedded steel. Chloride ions are present at varying levels in almost all aggregate and water sources; consequently, all concrete contains some chloride ions. The American Concrete Institute has established levels of acceptable chloride ions in concrete based upon service conditions.

The table below contains the recommendation of ACI 318 “Building Code Requirements for Structural Concrete.” In some cases, the aggregates and mix water contribute levels of chloride ions to the concrete that exceed ACI limits. In these instances Chryso®DCI® Corrosion Inhibitor may be added to the concrete mix to counteract the detrimental effects of the chloride ions. The use of Chryso®DCI® may be far less expensive to the concrete producer than finding alternate sources of materials. Technically, the producer may still be in violation of ACI maximum chloride limits, but Chryso®DCI® will counteract the potential corrosive effects of these unwanted chlorides so the producer and specifying engineer may allow its usage. In order to determine how much Chryso®DCI® to use, the concrete must be tested for water-soluble chloride ion content. After the chloride content is measured, the Chryso®DCI® dosage rate may be taken from the table below.

Chryso®DCI® Dosage Recommendations

Water Soluble Chloride Ion Content (lbs/yd3) Chryso®DCI® Dosage (gal/yd3)
0.00–0.50 0.50
0.51–0.75 0.75
0.76–1.00 1.00
1.01–1.25 1.25
1.26–1.50 1.50
1.51–1.75 1.75
1.76–2.00 2.00

Example: A prestressed concrete producer using a 705 lb cement factor mix tests for chloride content and finds that the mix contains 0.85 lb of chloride ions per cubic yard, or 0.12% by weight of cement. The chloride content percentage exceeds the ACI limit and the producer and the design engineer agree to use Chryso®DCI® to protect the embedded steel from corrosion. Locating 0.85 lb of chlorides per cubic yard on the table, 1.0 gallon of Chryso®DCI® per cubic yard is recommended.

Other Blog

Innovation
10/11/25

Type IL Cement and Concrete Bleeding Rates

Concrete bleeding rates are more closely tied to cement fineness than limestone content?  Many users blame…

Type IL Cement and Concrete Bleeding Rates
Innovation
03/11/25

Type IL Cement & Strength Performance

That T-IL cements don’t necessarily have lower strength performance compared to OPC? In fact, many producers…

Type IL Cement & Strength Performance
Innovation
30/10/25

Using Adfil®Strux: Case Studies

When a lonely Indiana road needed a hashtag fiber reinforced overlay, Chryso customer Smith Ready Mix,…

Using Adfil®Strux: Case Studies